Solid Insulated Switchgear (SIS 12kV SF6-Free)

Home  /  Products  /  Solid Insulated Switchgear (SIS 12kV)
100% SF6-Free • IP67 Solid Embedded Poles • -40°C Cold Proof

Solid Insulated Ring Main Unit (SIS 12kV / 24kV)

The eco-friendly successor to traditional SF6 gas-insulated switchgear. Primary live conductors, vacuum interrupters, and disconnectors are permanently encapsulated in epoxy resin and conductive EPDM shield, eliminating greenhouse gas regulations, pressure gauge monitoring, and cold-temperature gas liquefaction failure.

Solid Insulated Switchgear SIS 12kV
SIS-12 Solid Insulated Ring Main Unit (Modular C / V / F Units)
// Revolutionary Insulation

Why Global Utilities Are Switching from SF6 RMU to SIS

Sulfur hexafluoride (SF6) has a Global Warming Potential (GWP) of 23,500 and liquefies at sub-zero temperatures (causing catastrophic insulation breakdown below -25°C without tank heating). AIKey SIS uses solid embedded poles to provide complete environmental immunity.

  • ✓ IP67 Protection Degree: Live parts are completely sealed in APG epoxy resin casting. Fully flood-proof, dust-proof, and salt-fog resistant.
  • ✓ -40°C to +45°C Native Operation: No gas pressure monitoring, no gas refills, no SF6 heating resistors required in Siberian winters.
  • ✓ Visible Disconnect Gap: Mechanical visual observation window allows field operators to physically verify the three-position disconnect status before earthing.
  • ✓ Modular Plug-and-Play Expansion: Standard C (Load Switch), V (Circuit Breaker), and F (Fuse Combination) units connect seamlessly via solid shielded busbars.

Solid Insulated Switchgear Electrical Ratings & Characteristics (IEC 62271-200)

Technical Parameter Unit V Unit (Circuit Breaker) C Unit (Load Switch) F Unit (Fuse Combination)
Rated Voltage (Ur)kV121212
Rated Frequency (fr)Hz50 / 6050 / 6050 / 60
Rated Normal Current (Ir)A630 / 1250630125 (Fuse dependant)
Power Frequency Withstand Voltage (1 min)kV42 (to earth) / 48 (across gap)42 / 4842 / 48
Lightning Impulse Withstand (1.2/50μs)kV75 (to earth) / 85 (across gap)75 / 8575 / 85
Rated Short-Time Withstand Current (4s)kA20 / 2520 / 25—
Rated Peak Withstand Current (Ip)kA50 / 6350 / 6350 (with fuse)
Rated Short-Circuit Breaking CurrentkA20 / 25—31.5 (Fuse breaking)
Mechanical Endurance (Operations)Times10,000 (M2 Class)5,000 (M1 Class)3,000
Protection Degree (Primary High Voltage)—IP67IP67IP67
Protection Degree (External Enclosure)—IP4XIP4XIP4X
Operating Ambient Temperature°C-40°C to +45°C-40°C to +45°C-40°C to +45°C